PIS is multi-function integrated power supply,is able to realize power management and control.PIS-O outdoor type is of following functions:oil engine monitor,ATS power supply switch,choose 2 from 3 phase,non-contact stablizer,ACDB distribution unit,SPD protection,GSM control and alarm,fire alarm.PIS control adopt multi-processor,which are dependently and in connection.128*64 LCD screen is able to display kinds of PIS parameter,it is highly integrated and light. temp_PIS_2
PIS is 3 way power supply integrated management system( 1 way commercial electricity,2 ways oil engine).If commercial electricity is normal,ATS could choose commericial electricity firstly.phase selector could choose 2 qualified power suply,then provide power to load after AVR stablizing.Even there is phase lacking,it could also make sure the output of AVR.If commerical electricity is cut off,PIS could test voltage of storage battery. Oil engine monitor system start up oil engine 1and ATS choose running oil engine to supply power if storage battery is unable to meet requirements of load.Then oil engine 1 stop running as per regulated time,oil engine 2 begine to run.If one oil engine goes bad,it will stop running,and the other one begin to work.Two engines work by turns.Once commerical electricity becomes normal,oil engines could switch to commercial electricity. PIS Protection: anti-lighting,SPD protect,overvoltage protect,undervoltage protect,overload protect,short circuit protect,high frequency protect,low oil pressure protect,low oil position protect,low speed protect,fire protect,guardance protect,and temperature protect. GSM alarm function could inform manager by GSM message if there is fault,administer could act according to GSM.
Model |
Rated power (kVA) |
Dimension(mm) |
N.W.(kg) |
PIS-O-7.5 |
7.5 |
650*550*1550 |
190 |
PIS-O-10 |
10 |
650*550*1550 |
210 |
PIS-O-15 |
15 |
650*550*1550 |
250 |
PIS-O-20 |
20 |
750*650*1750 |
310 |
PIS-O-30 |
30 |
750*650*1750 |
450 |
Technical Data
|
Name |
PIS-O Outdoor Power Integrate Management System |
Rated capacity |
7.5kVA 10kVA 15kVA 20kVA 30kVA |
|
Input power |
2 way oil engine,1 way commercial electricity |
|
Input volt. frequency |
50Hz/60Hz |
|
Input volt. range |
AC400V±30% (AC280V-520V) or others |
|
Input volt.duty |
commercial power3Φ3W+G、oil engine 3Φ3W+N |
|
Output volt.duty |
Commercial power AVR output L+N+G、 Oil engine 3Φ3W+N+G |
|
Efficiency |
>99% |
|
Overload ability |
overload 50%,30min |
|
Working temp. |
-15℃ ~ +55℃ |
|
Relative Moisture |
RH 10%-90%(20℃±5℃) |
|
Latitude |
<3000m |
|
Ingress protection |
IP33 |
|
oil |
Oil engine control |
Start oil engine at fault of commerical electricity,2 oil engines could auto run by turns as design.Oil engine parameters are customerized. Manuel emergency start oil engine function is available |
Oil engine protection |
High water temp. protection Low oil press. protection Low oil position protection Overspeed,underspeed protection Overvoltage protection (0-300V setting) Undervoltage protection(0-300V setting) Overload protection(0-100A setting) |
|
3 phase/2 phase |
Choose superior better 2 phase according to commercial electricity,is able to make sure AVR normal run if lacking a phase,start oil engine at lowest limit. |
|
AVR non-contact voltage regulator |
Isolate output at commercial electricity input Input voltage AC400V±30%(280V-520V) Output voltage AC230V±5%(218V-242V) response time <40ms efficiency>99% overvoltage protection undervoltage protection overload protection |
|
ATS 3 power switch |
Choose a output according to input prior choice: |
|
MS 5 power swith |
Choose a output from following 5 powr supply by hand ATS 3 power switch Oil engine 1 input Oil engine 2 input Commercial electricity input AVR output |
|
PSD protection |
Protection function, rated 40~100kVA PSD pulse width 8-20uS Provide abate normally open dry contact output,remote alarm |
|
ACDB electricity distribution |
provide multi-switch to go with different load |
|
Monitor alarm |
able to monitor temperature,fire alarm,entrance guard |
|
GSM |
Send PIS alarm message by GSM net to users,receive control orders from users |